Electrical Fit-Off Inspection & Test Plan

Second-fix electrical inspection covering the installation of accessories, luminaires, switchgear and final circuit testing. Validates compliance prior to energisation and certificate of compliance.

15 checklist items
3 hold points
1 witness points
Use this template — it's free

Checklist Preview

Accessories & Fixtures

Requires sign-off
P/F
GPOs installed and correctly oriented
P/F
Light switches operating correctly
P/F
Luminaires installed per specification
P/F
Downlight thermal clearances maintained
Photo
P/F
Data outlets installed and labelled

Switchboard

Requires sign-off
P/F
Circuit breaker ratings per design
Hold
P/F
RCD protection installed per AS/NZS 3000
Hold
P/F
Circuit directory and labelling complete
P/F
Cable terminations torqued to specification

Testing & Commissioning

Requires sign-off
P/F
Insulation resistance test (minimum 1MΩ)
Hold
P/F
Polarity test satisfactory
P/F
Earth fault loop impedance within limits
P/F
RCD trip time within 300ms
Witness
#
Supply voltage within tolerance
Aa
Certificate of compliance number